APC UPS Time Remaining Value for N-Able

The APC service time remaining is calculated in 1000 of time ticks. the calculation is as follows.

The Time remaining threshold is currently showing a Value of 342.00 Time Ticks.

The mathematical calculation to determine how many minutes there are left will be

342 x 1000 = 342000
342000 / 100 time ticks =  3420 seconds
3420 seconds / 60 = 57 minutes

time remaining in minutes is 57 min.

The following illustrates the custom thresholds for:

Normal 10 min or more
Warning 5 min – 10 min
Failed 5 min or less